• Vacuum circuit breaker with Siemens same operating mechanism CT68 1
  • Vacuum circuit breaker with Siemens same operating mechanism CT68 2
Vacuum circuit breaker with Siemens same operating mechanism CT68 1
Vacuum circuit breaker with Siemens same operating mechanism CT68 2

12kV Fixed Vacuum Breaker with CT68 Operating Mechanism

Model: CT68-12

Description

Model CT68-12 indoor vacuum circuit breaker use with CT68 spring operating mechanism. It is three-phase AC, 50 Hz indoor power distribution equipment with the voltage of 12kV, mainly used in distributed power systems, mines, petroleum, chemical industry, metallurgy, construction, transportation, coal mines and municipalities, as well as in the power supply and distribution systems of urban residential buildings and public facilities and other places. It is widely used to protect high-voltage power equipment from over-current, short-circuit, under-voltage and over-voltage, and can reliably guarantee the safe operation of power equipment.
  • Features
  • Technical parameters

Features of CT68-12 vacuum circuit breaker

The CT68-12 vacuum circuit breaker adopts special contact material and interrupter with high breaking capacity and with very long electrical endurance.
The CT68-12 vacuum circuit breaker has simple structure, high breaking capacity, long endurance, all-round operating functions, no explosive danger and convenient maintenance. It is fit to control transport system and protect switch in powerhouse and transformer substation, especially fit to break important load or frequent operations in some places.

Applying Ambient Conditions
1.Height above sea level: not exceed 1000M.
2.Circumstance humidity: max +40°C, min -25°C.
3.Relative humidity: daily average <95%, monthly average≤90%.
4.Earthquake intensity: Degree 9.
5.Installation place: no fire, no explosive danger, no serious corrosion, and no frequent tense vibration.

Technical parameters of CT68-12 Vacuum Breaker

No. Item Unit Data
1 Rated voltage KV 12
2 Rated
insulation level
Short-time power frequency withstand voltage (1min) KV 42
Lightning impulse withstand voltage (peak) KV 75
3 Rated frequency Hz 50
4 Rated current A 630
1250
1250
1600
2000
2500
3150
1250
1600
2000
2500
3150
4000
5 Rated short-circuit breaking current (effective value) KA 20 25 31.5 40 50
6 Rated short-circuit withstand current KA 20 25 31.5 40 50
7 Rated short circuit duration s 4
8 Rated peak withstand current KA 50 63 80 100 125
9 Rated short-circuit making current KA 50 63 80 100 125
10 Rated short-circuit breaking times times 50 30 20
11 Secondary circuit power frequency withstand voltage (1min) V 2000
12 Rated single capacitor bank breaking current A 630 800 800
13 Rated back-to-back capacitor bank breaking current A 400

Below drawing is for CT68-12/3150-40-275, for reference

CT68-12-3150-40-275 VCB drawing

 

Get In Touch